whatsapp
Brand KRYKARD UPS System Industrial UPS KRYKARD Make 60 KVA 3:3 Phase On-Line UPS

KRYKARD Make 60 KVA 3:3 Phase On-Line UPS

EH 33-060

UPS System Industrial UPS

Price: 497960

You save 250160

  • KRYKARD brings you a well-engineered Industrial Online UPS backed by timely service to deliver reliable perfect minimum downtime. It is loaded with extra protection features like Short-circuit, Over load, Over Temp, Battery Low, Voltage, Over Voltage, Under Voltage, Fan Failure. KRYKARD EH 33 Series UPS is available in various options like SNMP, RS485, Parallel Redundancy Function ( x 6 units). It has the best-inclass display functions which include LCD+LED display, multifunctional keys operation, friendly human-machine interface. It comes with Standard Emergency power off (EPO) & Standard maintenance bypass features.
  • Static Converter for automatic data processing machines
  • Advanced 3-level technology and dual-core DSP control technology
  • Active power factor correction (APFC), input PF up to 0.99
  • Improved system efficiency up to 95%
  • Output PF as Unity
  • Advanced digital and parallel technology, providing higher reliability
  • Wide input voltage range from 304Vac to 478Vac on full load
  • Linear derating during very low voltages up to 228V input, reducing battery usage & extending battery service life
  • 50 / 60Hz frequency auto-sensing & frequency conversion mode

  • Reset default

    Specification

    Output Specification
    Output Capacity (KVA )
    60 KVA
    Output Capacity (KW )
    60 KW
    Output Power Factor
    1 Power Factor
    Output Phase
    3 Phase
    Output Voltage
    400 Volt
    Other Output Voltage
    380 Or 415 Volt
    Efficiency at Full Load
    > 99 %
    Output Voltage Distortion
    < 3 %
    Output Frequency (sync to mains)
    50/60Hz +/- 3 Hz
    Output Frequency (not synced)
    +/- 0.1% for 50/60Hz Nominal
    Load Crest Factor
    3:1
    Output Voltage THD
    < 3% linear load and <5% non-linear load
    Transfer Time
    < 0 ms
    Output Waveform type
    Sine Wave
    Output Connections
    Hard Wire 5-wire (3PH + N + G)
    Bypass
    Built-in Maintenance Bypass
    Overload Capacity
    150% for 1 minute 125% for 10 minutes
    UPS Parallel Upto
    4 Nos.
    Input Specification
    Input Voltage
    400 Volt
    Input Phase
    3 Phase
    Input frequency
    50 Or 60 Hz
    Input frequency Range
    45 - 65 Hz
    Input Voltage Range (Output Derated)
    380 - 415 Volt
    Input voltage range for main operations
    304 - 477 Volt
    Input Power Factor
    0.99
    Input Connections
    Hard Wire 5-wire (3PH + N + G)
    Input Protection
    Circuit Breaker & Fuse
    Input Voltage THD
    < 3 %
    Input Short Circuit Current (Maximum)
    10 kAmps.
    Batteries & Runtime
    Maximum Charger Capacity
    24 Amp.
    Battery DC Bus
    384 - 528 VDC
    Battery Type Compatibility
    SMF Battery
    Battery Position Option
    External
    Approved Battery Capacity (AH)
    17 - 200 Amp.
    Battery Circuit Breaker
    Optional
    Communication & Management
    Control panel
    Touch Screen LCD User Interface
    SNMP Management
    Optional
    Audible Alarm
    Audible and visible alarms prioritized by severity
    Physical
    Maximum Height
    885 Mm
    Maximum Width
    360 Mm
    Maximum Depth
    950 Mm
    Net Weight
    96 Kg
    Environmental
    Operating Temperature
    0 - 40 °C
    Operating Relative Humidity
    0 - 95 %
    Operating Elevation
    0 - 984.3 Meters
    Storage Temperature
    -15 - 40 °C
    Storage Relative Humidity
    0 - 95 %
    Storage Elevation
    0 - 14763.3 Meters
    Online thermal dissipation
    900 Btu/Hr
    Protection Class
    IP20
    Compliances
    Compliance
    BIS
    Approvals
    CE, EAC, IEC 62040-1-1, IEC 62040-2, IEC 62040-3, IEC 62040-4, ISTA 2B, RCM, WEEE
    Other Environmental Compliance
    Compliant
    Other Specifications
    Technology
    Double Conversion Online
    Filtering
    Full time multi-pole noise filtering : 0.3% IEEE surge let-through : zero clamping response time : meets UL 1449
    Surge Protection
    Yes

    Documentation

    Item Catalogue
    krykard_make_industrial_UPS
    pdf

    Options