whatsapp
Brand Vertiv UPS System Industrial UPS Vertiv Liebert Make 40 KVA 3:3 Phase Rack/Tower Mountable On-Line UPS

Vertiv Liebert Make 40 KVA 3:3 Phase Rack/Tower Mountable On-Line UPS

ITA 40KVA

UPS System Industrial UPS

Price: 409460

MRP 726054 You save 316594

Compact, Efficient, and Reliable Power Solution

  • Liebert ITA is a full featured transformer free scalable UPS designed to oer compact, efficient and reliable power to power thirsty modern electronic gadgets. It features double conversion online design that ensure continuous high quality power even when the main AC power fails.
  • Utilize state of the art technology and components to withstand fluctuation of input main voltage. Extra wide input voltage and frequency range eectively reduces the discharging period of battery; thus prolong battery life
  • Deliver 0.9 Power factor that can power 10-20% more load then traditional UPS, makes it suitable for latest server models. Additionally its high power density allows the rack to have a smaller footprint. Liebert ITA uses soft-wire parallel operation mode without the need for complex parallel subrack, allowing the user to save on system cost
  • Liebert ITA achieves up to 95% efficiency in double conversion mode and up to 98.5% in ECO mode ensuring effective load protection while reducing the total cost of ownership (TCO) and environmental impact
  • FEATURES

  • IGBT Based Rectifier
  • Advanced DSP Based Technology
  • 0.9 output power factor
  • Double conversion efficiency up to 95%
  • ECO mode efficiency up to 98.5%
  • High capacity battery charger 30-40kVA ~ 6kW
  • Dynamic Design; Rack/Tower convertible
  • ITA 5-20kVA scalable up to 4 units in N+X configuration
  • Integrated parallel load bus and synchronization port (LBS)
  • Phase compatibility 5/6/10kVA: 1/1 or 3/1 phase 20kVA: 3/1 or 3/3 phase 30-40kVA: 3/1 or 3/3 phase
  • Comprehensive value added options including LPD, UPD etc
  • Easy site installation and configuration

  • Reset default

    Specification

    Output Specification
    Output Capacity (KVA )
    40 KVA
    Output Capacity (KW )
    40 KW
    Output Power Factor
    1 Power Factor
    Output Phase
    3 Phase
    Output Voltage
    400 Volt
    Other Output Voltage
    380 Or 415 Volt
    Efficiency at Full Load
    > 95 %
    Output Frequency (sync to mains)
    50/60Hz +/- 3 Hz
    Load Crest Factor
    3:1
    Output Waveform type
    Sine Wave
    Output Connections
    Hard Wire 5-wire (3PH + N + G)
    UPS Parallel Upto
    4 Nos.
    General Specifications
    Isolation Transformer
    Optional
    Paralleling Options
    Yes
    Flexible Battery Option
    Yes
    Paralleling Kit for Synchronising
    Optional
    Input Specification
    Input Voltage
    400 Volt
    Other Input Voltage
    380 Or 415 Volt
    Input Phase
    3 Phase
    Input frequency
    50 Or 60 Hz
    Input frequency Range
    40 - 70 Hz
    Input Voltage Range (Output Derated)
    290 - 498 Volt
    Input voltage range for main operations
    340 - 498 Volt
    Input Power Factor
    0.99
    Input Connections
    Hard Wire 5-wire (3PH + N + G)
    Batteries & Runtime
    Approved Battery Capacity (AH)
    42 - 200 Amp.
    Battery Circuit Breaker
    Optional
    Maximum Charger Capacity
    12 Amp.
    Battery DC Bus
    384 - 480 VDC
    Battery Type Compatibility
    SMF Battery
    Communication & Management
    Control panel
    LCD Display
    Interface Port(s)
    RS-232, USB
    SNMP Management
    Optional
    Power Management Software
    Optional
    Audible noise at 1 meter from surface of unit
    < 58 Decibal
    Physical
    Maximum Height
    800 Mm
    Maximum Width
    176 Mm
    Maximum Depth
    485 Mm
    Net Weight
    72 Kg
    Environmental
    Operating Temperature
    0 - °C 40
    Operating Relative Humidity
    0 - % 95
    Protection Class
    IP20
    Other Specifications
    Technology
    Double Conversion Online

    Documentation

    Item Catalogue
    ITA 40KVA
    pdf

    Options

    Contact Us