Specification
Output Capacity (KVA )
6 KVA
Output Capacity (KW )
4.8 KW
Output Power Factor
.8 Power Factor
Other Output Phase
Or Phase
Other Output Voltage
200 Or 230 Volt
Efficiency at Full Load
> 88 %
Output Voltage Distortion
< 3 %
Output Frequency (sync to mains)
50/60Hz +/- 3 Hz
Output Frequency (not synced)
+/- 0.1% for 50/60Hz Nominal
Output Waveform type
Sine Wave
Output Connections
Hard Wire 3 wire (1PH+N+G), Hard Wire 5-wire (3PH + N + G)
Bypass
Internal Bypass (automatic & manual)
Overload Capacity
Optional
Flexible Battery Option
No
Isolation Transformer
In-Built
Paralleling Options
Not Available
Rack Mounting Kit
Optional
Paralleling Kit for Synchronising
Not Available
Other Input Voltage
200 Or 230 Volt
Other Input Phase
Or Phase
Input frequency
50/60Hz +/- 3 Hz
Input Voltage Range (Output Derated)
- Volt
Input voltage range for main operations
176 - 300 Volt
Input frequency Range
40 - 60 Hz
Input Connections
Hard Wire 5-wire (3PH + N + G)
Input Protection
Resettable Circuit Breaker
Approved Battery Capacity (AH)
7 - 100 Amp.
Maximum Charger Capacity
8 Amp.
Battery Position Option
External
Internal Battery Capacity (VAH)
VAH
Battery Type Compatibility
SMF / Flooded Batteries
Batteries Recharge Time upto 90%
< 8 Hrs.
Communication & Management
Control panel
LED status display
Power Management Software
Optional
Interface Port(s)
DB-9 RS-232, Smart-Slot
Audible Alarm
Audible and visible alarms prioritized by severity
Audible noise at 1 meter from surface of unit
< 55 Decibal
Operating Temperature
0 - 25 °C
Operating Relative Humidity
0 - 95 % Rh
Operating Elevation
- Meters
Storage Temperature
- °C
Storage Relative Humidity
- % Rh
Storage Elevation
- Meters
Compliance
IS 16242 (Part1): 2014
Approvals
IS 16242 (Part1): 2014
Other Environmental Compliance
IS 16242 (Part1): 2014
Technology
Double Conversion Online
Filtering
Full time multi-pole noise filtering : 0.3% IEEE surge let-through : zero clamping response time : meets UL 1449